Specifications

1.power quality analyzer
2.Power Analyzer
3.Dimension:200x100x58mm
4.Resolution Accurancy:0.1,0.15
5.Net Weight:0.98kg

power quality analyzer / Three-phase power quality analyzer/power analyzer meter / digital power analyzer

 WFTD-3000 Power quality analyzer is a portable and easy-to-operate meter which is used to analyze and record power quality. It real time display, record and analyzes data of the single-phase or 3-phase, and displays the voltage and current in waveform

Technical Specifications

Alternating Voltage

Three-phase alternating current input (3 differential input: L1-N1, L2-N2, L3-N3)

Input voltage range

3—550 VRMS L-N, 3—900 VRMS L-L

Accuracy

Measuring range 1:
Measuring range 2:
Measuring range 3:
Measuring range 4:

5.0 VRMS—70.0 VRMS: ±1% ±0.5V
10.0 VRMS—130.0 VRMS: ±1% ±0.8V
20.0 VRMS—300.0 VRMS: ±1% ±1.5V
30.0 VRMS—550.0 VRMS: ±1% ±2.5V

Crest factor

<1.4

Frequency range

45—66HZ

Resolution

0.1V

Alternating Current

Three-phase alternating current input

Measuring range 1:

Input current
Resolution
Accuracy
Crest factor

0.004—0.1 VRMS: use for 4—100A current range
0.1A
±(2%rdg + 0.3A)
<2.3

Measuring range 2:

Input current
Resolution
Accuracy
Crest factor

0.04—1 VRMS: for current range 40—1000A
0.1A
±(2%rdg + 3A)
<2.3

Power Measurement

Measured parameters

Active Power(P), Reactive Power(Q), Apparent Power(S)
Power Factor Cosφ , Energy(Wh, Vah, Varh)

Accuracy

Power
Power factor

±(3% + 3dgt)
0.00—0.39 :±0.06
0.40—1.00:±0.06

All tests were performed in 4-quadrant: capacitance or inductance load or generator.

Voltage Harmonic Measurement

Measuring range

UM>3%UN

Resolution
Accuracy

0.1%
5%UM (DC 3%)

Measuring range

UM<3%UN

Resolution
Accuracy

0.1%
0.15%UN

UN :

Nominal voltage(True RMS)

UM :

Measured harmonic voltage hM = 1—50