| SmartReader 7 Specifications |
| No. of Channels | |
| Clock Accuracy | +/- 2 seconds per day |
| Memory Size | 32 KB (32,767 readings) |
| Sampling Methods | 1. Continuous (First-in, First-out) 2. Stop when full (Fill then stop) |
| Sampling Rates | User selectable rates from 8 seconds to once every 5 days |
| Resolution | 8-bit |
| Operating Limits | -40 to 70°C (-40 to 158°F) and 0 to 95% relative Humidity |
| Accuracy | +/- 1% of full scale |
Input Ranges (Standard Model) | 0 to 2.5 volts DC (1 channel) 0 to 5.0 volts DC (2 channels) 0 to 10.0 volts DC (1 channel) 0 to 200 millivolts DC (1 channel) 0 to 25 milliamps DC (2 channels) |
|
Input Ranges (Other Models) | 0 to 2.5 volts DC (all external channels) 0 to 5 volts DC (all external channels) 0 to 10 volts DC (all external channels) 0 to 25mA DC (all external channels) |
|
| Input Impedance | > 1 M ohm (200 mV channels) > 1 M ohm (0 to 2.5 V channels) 20 K ohm (0 to 5.0 V channels) 40.9 K ohm (0 to 10.0 V channels) 100 ohm (0 to 25 mA channels) |
|
| Transducer Restrictions | | It is recommended to use a single power supply or loop isolators to avoid ground loops. |
|
| Maximum Overload Protection | | Voltage Channel: | +/-40 Volts (reverse-polarity protected) | | Current Channel: | +/-70 mA (reverse-polarity protected) |
|
| External Connector | Removable screw-type terminal strip with common (-) connection |
| General Specifications | Size | 60 mm x 48 mm x 19 mm (2.4" x 1.9" x 0.7") |
| Case Material | Noryl plastic |
| Mounting | Magnetic backing and locking eyelet |
| Power Source | Battery | 3.6 volt Lithium, 1 Amp-Hour |
| Battery Life | 10 Years under normal use |
| Internal Temperature Sensor | Type | NTC thermistor (10,000 ohms @ 25°C [77°F]) |
| Range | -40 to 70°C (-40 to 158°F) |
| Accuracy | +/- 0.2ºC over the range: 0 to 70ºC (+/- 0.3ºF over the range: 32 to 158ºF) |
| Resolution | 0.4ºC (0.7ºF) @ 25ºC; better than 1ºC (1.8ºF) between -25 and 70°C (-13º and 158ºF); better than 2.0ºC (3.6°F) between -40 and -25°C (-40ºF and -13ºF) |