Product Description

  • Analysis for Single Phase and Balanced 3 phase system

  • True RMS Value(V and I)

  • Active Power(K,KW,MW,GW)

  • Apparent(VA,KVA,MVA) and Reactive Power (VAR,KVAR,MVAR)

  • Power Factor(PF),Phase Angle( Φ )

  • Energy(WH,KWH,KVARH,PFH)

  • Programmable PT(1 to 3000)Ratios

  • Display of Overlapped Voltage and Current Waveform

  • Maximum Demand (MD in W,KW,MW)with programmable Period

  • Harmonic Analysis (V and I) to 50th Order

  • Display of 25 Harmonics in one screen

  • Optical Isolated RS-232C Interface

  • Smart Datalogging to save Battery

  • Datalogging of 32,64,128 or 256 points/cycles

  • Analysis of Tatal Harmonic Distortion(%THD-F)

  • Graphic Phasor Diagram

  • Capture 128 Transient Events(Time+Cycles+Faults) with Programmable Threshold(%),also can be reviewed in LCD

  • 50000 Records with Programmable Intervel (1 to 6000 seconds)

  • Real-time Output of Wavaform,Power Parameters and Harmonics at Command

  • Large Dot Matrix LCD Display with Backlight

  • Power for Long-term Monitoring

  • Built -in Calendar Clock for Data Logging

AC Current (50 or 60 Hz, Auto Range, True RMS)
Range
Resolution
Accuracy of Reading
4.0 V - 1500.0 A
0.01 A
± 0.5 % ± 5 dgts

AC Voltage (50 or 60 Hz, Auto Range, True RMS)

Range
Resolution
Accuracy of Reading
4.0 - 600.0 V
0.1 V
± 0.5 % ± 5 dgts

Harmonics of AC Voltage in Percentage and Magniude(1 to 50th order)

Range
Resolution
Accuracy(in%)

Accuary

(in Magnitude)

1 – 20 th
0.1 %
± 2 %
± 2 % ± 0.5 V
20 – 50 th
0.1 %
4 % of reading ± 2 %
4 % of reading ± 0.5 V

Hamonics of AC Current in Percentage and Magnitude (1 to 50th order)

Range
Resolution
Accuacy(in %)

Accuracy

(in Magntude)

1 – 20 th
0.1 %
± 2 %
± 2 % of reading ± 0.4 A
20 – 50 th
0.1 %
4 % of reading ± 2 %
± 4 % of reading ± 0.4A

Power Factor(PF)

Range
Resolution
Accuracy(>20 V and >20 A)
0.000 - 1.000
0.001
± 0.04

Phase Angle ( Φ )

Range
resolution
Accuracy(>20 V and >20 A)
-180 ° to 180 ° (0 ° to 360 ° )
0.1 °
±1 °

Total Harmonic Distortion(%THD-F,1 to 50th order)

Range
Resoluion
Accurary(>20 V and >20 A)
0.0 - 20%
0.1%
± 2 %
20 - 100%
0.1%
± 6 % of reading ± 1 %
100 - 999.9%
0.1%
± 10 % of reading ± 1 %

Crest Factor (C.F.)

Range
Resolution
Accuracy of Readings
1.00 - 99.99
0.01
± 5 % ± 30 digits

AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1)

Range
Resolution

Accuracy of Readings

(>20V and >20A)

10.0 - 999.9 W
0.1 W
± 1% ± 20 dgts
1.00 - 9.999 KW
0.001 KW
± 1% ± 20 dgts
10.00 - 99.99KW
0.01 KW
± 1% ± 20 dgts
100.0 - 999.9 KW
0.1 KW
± 1% ± 20 dgts
1000 - 9999 KW
1 KW
± 1% ± 20 dgts

General Specification:

Conductor Size55mm(approx.),64*24mm(bus bar)
Battery Typetwo 1.5 V SUM-3
Display128*64 Dot Matrix
Power Consumption10 mA(approx)
Auto - Power - Off30 minutes after power-on
Update time2 times/sec.(display)
No. of Sameples per Period512(voltage or current),256(power)
Operating Temperature-10 ℃ to 50 ℃
Operating Humidity<85% RH
Storage temperature-20 ℃ to 60 ℃
Storage Humidity<75% RH
Dimension210 mm (L) * 62 mm (W) * 35.6 mm (H),8.3"(L) * 2.5 "(W) * 1.4"(H)
Weighttest leads *1 pair、Carrying bag*1、Users manual*1 、Batteriews 1.5V*2
Accessories640g


Item added to Inquiry Cart